HBD-D5015A® energy storage system primarily adopts a highly integrated design, incorporating battery clusters, distribution cabinets, liquid cooling units.and fire protection systems all installed within a 20-foot container for ease of transportation.
The system features independent power supply, cooling, and fire protection systems

HBD-D5015A® energy storage system primarily adopts a highly integrated design, incorporating battery clusters, distribution cabinets, liquid cooling units.and fire protection systems all installed within a 20-foot container for ease of transportation. The system features independent power supply, cooling, and fire protection systems.
HBD® is mainly developed for no emission and low noise, Reduce the dependence on grid, Improve power supply quality and Ensure the power consumption of emergency load.
High Density: 5.015MWh in a standard 20ft container (using 314Ah cells), maximizing space efficiency for shipping.
High Safety: Triple-level (PACK, cluster, cabin) fire protection; multi-level fusing; IP67-rated battery packs.
High Efficiency: Smart thermal management; real-time remote monitoring and early warning for reliable operation.
3 years after export from the factory or the Energy Throughput achieve 4590kWh per kWh which comes first;

|
General Information |
||
|
Rated Battery Storage Capacity |
5015 kWh |
|
|
Battery Stack |
12*1P416S |
|
|
Rated Voltage |
1331.2VDC |
|
|
DC Voltage Range |
1164.8VDC~1497.6VDC |
|
|
Charge/D is charge Rate |
0.5P |
|
|
Protection Class |
IP54 |
|
|
Loading Dimension(W*D*H) |
2438mm*6058mm*2896mm(ISO 20’HQ) |
|
|
Net.Weight |
44000 kG |
|
|
Loading Capacity |
20’GP |
1 units |
|
Discharge Temperature Range |
-20~50°C(> 40℃ derating) |
|
|
Humidity |
0~95%(No Condensation) |
|
|
Max Altitude |
≤2000m |
|

|
Battery |
|
|
Cell Type |
LFP(LiFePO4) |
|
Cell Capacity |
314Ah |
|
Pack Capacity |
104.5 kWh |
|
Pack Rated Voltage |
332.8 VDC |
|
Cyclic Life |
8000 Times(0.5C@80%DOD) |
|
Battery Voltage of Rack |
1331.2 VDC |
|
Rack Capacity |
417.99 kWh |
|
Connection of Rack |
12*1P416S
|
|
Cooling System |
|
|
Battery Cabin |
Liquid Cooling |
|
Liquid-cooled unit |
60kW |
|
Quantity |
1 |
|
Protection Device |
|
|
Fire Suppressant |
Aerosol (CE),water inlet valve reserved |
|
DC Side |
Disconnect Switch &Fuse |
|
Sensor |
Smoke,temperature,Gas detector |
|
High-Voltage Box |
|
|
High-Voltage Box |
250A/1500V |
|
Quantity |
12 |
|
BMS |
|
|
Battery Manage ment Number |
52 |
|
Battery Balancing Method |
Passive Balancing |
|
Battery Balancing Current |
≤100mA |
|
Other |
|
|
Communication Interface |
Modbus TCP |