MGSB-60kW-100kWh Microgrid Solution

 

  • System Maximal Output Power 120kVA
  • Loading Dimension(W*D*H) 4000*1130*2000mm
  • Loading Capacity of 40’ HC 6 units
  • Standard to be Followed AS 3000/ EN 50549 for PCS
description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Product Description
Design Standards

Model: MGSB-60-100

MICRO-GRID SOLUTION

Design Standards
MGSB® is a new range of secure integrated hybrid microgrid solution. With diesel generator, battery storage and solar inverter in one secure unit. MGSB® is mainly developed for lower emission, reducing the dependence on main power and decreasing the consumption cost.
Benefits
· Integrated installation, convenient storage and transportation;
· High return on investment and quick return;
· Simple operation and easy maintenance;
· Power and capacity can be expanded, meet different user needs;
· Accept customer customization, suitable for various scenarios;
Warranty
Battery Performance: 6000 cycles(80% DOD) or 2 years after manufacture;
Generator: 18 months after manufacture or 1500 hours running time;
Benefits

General Specification

System Rated Output Power

60kVA/48kW

System Maximal Output Power

120kVA

Rated Output Voltage

Minimal

380V@50Hz,3ph.

480V@60Hz,3ph.

Maximal

415V@50Hz,3ph.

480V@60Hz,3ph.

Battery Storage Capacity

100kWh

PV Output Power

MAX. 50kVA

Output Terminals

Copper terminals & CEE 125A/5P Socket

Loading Dimension(W*D*H)

4000*1130*2000mm

Net.Weight

Max.4500kg

Loading Capacity of 40’ HC

6 units

Discharge Temperature Range

-20℃~50℃

Standard to be Followed

AS 3000/ EN 50549 for PCS

 

  • THE HIGHEST PRIORITY:BESS & PV sharing load while Diesel generator standby.
  • When the BESS is lack of power, PV & Diesel generator will sharing load. The excess power from the PV will charge the battery.
  • When the PV is unstable, BESS will take the load of sharing load with diesel generator. *The diesel generator always be the standby power source.

Basic Logic

Power Priority

Highest

Secondary

Back Up

PV

Battery

Generator

Functions

Take load/charge

Take load

Take load/charge

    

Features

Generator Set

Prime Power

48kW / 60kVA

Rated Voltage

380~415V@50HZ

Engine to Ref.

FPT / PERKINS / CUMMINS .etc.

Emission

According to Customer Requirements

Fuel Consumption

15 L/h@100% load(Average value)

Fuel Tank Capacity

200L Bunded

Controller

AGC 150

Base Functions

Automatic Start-up / Alarm / Automatic Stop / 

Emergency Stop / Load Management

Energy Storage Battery

Cell Type

LFP(LiFePO4)

Pack Model

MF51280

Pack Capacity

14.336 kWh

Pack Rated Voltage

51.2 VDC

Discharge Depth

90%

Charger/Discharge Current

140 A(0.5C)

Battery Cluster Voltage

358V~755.3V

Rated Cycle Life

≥6000(80% DOD)

Hybrid Inverter System

Solar Converter

MAX. 50kVA

PCS

60kW(Max .66kW)

EMS

ASC 150

DC Voltage Range

150~750Vdc(Full load @350~750Vdc)

Max.Charge/Discharge Current

180A

Max.Conversion Efficiency

97.3%

PCS Output

3W4P+PE

STS(OPTION)

100kW for Seamless switching

Certification

EN 50549,CE,FCC

 

Options

Engine

Alternator

Fuel System

Generator Controller

Water Jacket Preheater Oil

 Preheater
Oil manual pump

PMG excitation
Space heater
Winding temperature
measuring

12 / 24 hour base tank
External fuel tank
Automatic fuel feeding
Switch between external
tank and base tank (three-way valve)

Deepsea, ComAp, Smartgen 

etc . controller
Tools with the machine

CONTACT US