Model:MGSB-250-400
MICRO-GRID SOLUTION
General Specification |
|||
System Rated Output Power |
250kVA/200kW |
||
System Maximal Output Power |
500kVA |
||
Rated Output Voltage |
Minimal |
380V@50Hz,3ph. |
380V@60Hz,3ph. |
Maximal |
440V@50Hz,3ph. |
440V@60Hz,3ph. |
|
Battery Storage Capacity |
400kWh |
||
PV Output Power |
According to Requirements |
||
Output Terminals |
Copper terminals & CEE 125A/5P Socket |
||
Loading Dimension(W*D*H) |
ISO 20 ’GP Container |
||
Net.Weight |
Max. 18000kg |
||
Loading Capacity of 20’GP |
1 unit |
||
Discharge Temperature Range |
-20℃~50℃ |
||
Standard to be Followed |
IEC 62477 & IEC 61000 for PCS |
Power Priority |
Highest |
Secondary |
Back Up |
PV |
Battery |
Generator |
|
Functions |
Take load/charge |
Take load |
Take load/charge |
Generator Set |
|
Prime Power |
200kW / 250kVA |
Rated Voltage |
380~415V@50HZ |
Engine to Ref. |
FPT / PERKINS / CUMMINS .etc. |
Emission |
According to Customer Requirements |
Fuel Consumption |
58 L/h@100% load(Average value) |
Fuel Tank Capacity |
800L Bunded |
Controller |
AGC 150 |
Base Functions |
Automatic Start-up / Alarm / Automatic Stop / Emergency Stop / Load Management |
Energy Storage Battery |
|
Cell Type |
LFP(LiFePO4) |
Pack Model |
MF51280 |
Pack Capacity |
14.336 kWh |
Pack Rated Voltage |
51.2 VDC |
Discharge Depth |
90% |
Charger/Discharge Current |
140 A(0.5C) |
Battery Cluster Voltage |
627.2V~806V |
Rated Cycle Life |
≥6000(80% DOD) |
Hybrid Inverter System |
|
Solar Converter |
According to Requirements |
PCS |
250kW(Max .300kW) |
EMS |
ASC 150 |
DC Voltage Range |
580~ 1000Vdc |
Max.Charge/Discharge Current |
432A |
Max.Conversion Efficiency |
98.9% |
PCS Output |
3W4P+PE |
STS(OPTION) |
N/A |
Certification |
CE |
Engine |
Alternator |
Fuel System |
Generator Controller |
Water Jacket Preheater Oil Preheater |
PMG excitation |
12 / 24 hour base tank external tank and base tank (three-way valve) |
Deepsea, ComAp, Smartgen etc . controller |